Newsletter | Infrastructure Study + 1 post(s) |
Posted: 26 Oct 2015 07:40 PM PDT PURPOSE OF STUDY The purpose of the study was to establish the ability of the existing electrical and mechanical systems infrastructure to support the current and future campus electrical and HVAC loads. To establish these criteria an assessment of the office space and data center loads was conducted. A matrix (table 7) was compiled that listed both current and projected loads by space type. EXECUTIVE SUMMARY The study has established that the electrical and mechanical infrastructure cannot support the future or current demands of the campus. This study lists infrastructure upgrades for consideration that will upgrade the campus M&E infrastructure to levels commensurate with the campus demands. MECHANICAL SYSTEM Current System Laboratory Loads The laboratory loads have been projected to increase in the future. The quantities in kilowatts (kW) are listed below. Building Existing Laboratory Loads (kW) Building Projected Laboratory Loads (kW) HVAC System Upgrades Option #1 – Baseline Model This option increases the existing air-cooled chiller capacity to support the increase in electrical equipment load. This option also replaces the air-cooled DX roof mounted AHU's with chilled-water AHU’s. It is assumed that all DX equipment will be replaced with chilled water equipment, including replacing the existing DX units in IDF rooms with fan coil units. The Table 1 below shows the energy consumed by the HVAC system for this option. The table is split to show the HVAC system power required to condition loads that operate 24/7 (electric rooms, IDF, labs), and power required to condition general office loads. Table 1. Projected HVAC Systems Power Input (kW) – Air Cooled Chiller Pros 1. Least expensive first cost. Cons Option #2 – Cooling Tower Chilled-Water Central Plant A central plant with high efficiency water-cooled chillers and cooling towers with variable frequency drives sized to support all cooling loads. Chilled water will be distributed to new high efficiency VAV roof mounted AHU's and to fan coil units throughout the buildings. Table 2 below shows the energy consumed by the HVAC system for this option. Table 2. Projected HVAC Systems Power Input (kW) – Cooling Tower Chilled-Water Plant Pros 1. Much more energy efficient than option #1 (baseline) Cons 1. More expensive first cost than option #1 Option #3 – 100% Geothermal Chilled-Water Central Plant A central plant with high efficiency water-cooled VFD chillers with geothermal bores sized to support all campus loads, (no cooling towers). Chilled water will be distributed to new high efficiency VAV roof mounted AHU's and fan coil units throughout the buildings. Table 3 below shows the energy consumed by the HVAC system for this option. Table 3. Projected HVAC Systems Power Input (kW) – 100% Geothermal Chilled-Water Plant Pros 1. Much more energy efficient than option #1 (baseline) & option #2 Cons 1. First cost highest of all options. Option #4 – Geothermal Hybrid Chilled Water Central Plant A central plant with high efficiency water-cooled VFD chillers with geothermal bores sized to support all 24/7 loads, and cooling towers with variable frequency drives to support all non 24/7 cooling loads. Chilled water will be distributed to new high efficiency VAV roof mounted AHU's and fan coil units throughout the buildings. Table 4 below shows the energy consumed by the HVAC system for this option. Table 4. Projected HVAC Systems Power Input (kW) – Geothermal Hybrid Chilled-Water Plant Pros 1. Much more energy efficient than option #1 (baseline) & option #2 Cons 1. First cost higher than option #1 & #2 Following is a life cycle costs analysis comparing all 4 options. The second table compares the option with no federal tax depreciation and no savings by design rebate. ELECTRICAL SYSTEM Current System Load Analysis The existing electrical services are currently overloaded. Refer to appendices A1 through D1. Below is the representation of the appendix in percentage. • Building A: 65% overloaded Projected Load Increase – short term (equipment only) The numbers below is based on the information provided by Symantec. • Building A: 34% projected load increase Potential Load Increase – long term (equipment only) For the longer term, a minimum of 10% was added for potential long term load increase. • Building A: 13% projected additional load increase in the long term HVAC Replacement Option # 0 (baseline model) Pros: Cons: HVAC Replacement Option # 1 (Chilled Water Central Plant) Pros: Cons: HVAC Replacement Option # 2 (100% Geothermal Chilled Water Central Plant) Pros: Cons: HVAC Replacement Option # 3 (Hybrid Geothermal Chilled Water Central Plant) Pros: Cons: The post Infrastructure Study appeared first on Poltrona. |
A Geothermal Feasibility Guide Posted: 26 Oct 2015 07:34 PM PDT Introduction The purpose of this report is to establish if a geothermal field can provide a medium for cooling chiller condenser water either in lieu of, or as a supplementary source to, the existing and future cooling towers. Alternate methods of cooling and heating provided by a geothermal field will save energy and dramatically reduce water consumption. This study also seeks to establish if water circulated through a geothermal field can provide precooling / preheating for the large amounts of outside air supplied to the current and future labs. This report evaluates the current thermal performance of the existing systems to determine the geothermal fields needed capacity to support both the current and future needs of the buildings infrastructure. The thermal systems analyzed include the cooling tower, chiller and boiler systems located in the central plant. Overview The current building systems consist of three chillers rated at 500 tons (2) and one chiller at 88 tons, for a total connected tonnage of 1088 tns. There is one cooling tower rated at 600 tons that is inadequately sized to support heat evaporation for the 1088 tns chiller capacity. The under sized cooling tower prevents the chillers from providing their maximum cooling capacity and degrades their operating efficiency, increasing energy consumption. Current water consumption can exceed the 25,000 gal/day limit imposed by the water authority. Future additional building will require approximately 300 tons of additional cooling and additional 780,000 gal/yr of water for evaporation via cooling towers. Additional water is also required for chemical treatment and regular blow down of total dissolved solids. Executive Summary Geothermal Field EXISTING CHILLER PLANT CAPACITY AND EFFICIENCY The existing chiller plant consists of three chillers as follows 500 tns (2) 88 tns (1), for a total chiller tonnage of 1088 tns. The existing cooling tower however is derated due to compromised airflow, and is also undersized by approximately 488 tns. The net result is that the connected chillers cannot reach their rated capacity and have reduced efficiency. It is estimated that the current system is operating at approximately 1.45 KW/TN. Providing the existing machines with geothermal water at approximately 61 deg will increase the chiller efficiency by almost 100 % to around 0.76 KW/TN. Combined water savings due to no evaporation through the cooling tower will be around 5,837,168 gal/yr. The annual energy cost reductions and life cycle cost analysis are as follows; Option #2 provides 57% (500 tns, or 1 chiller) of cooling capacity from the geothermal field. For the total connected chiller loads for both new & existing buildings, would have a pay back of 4.4 years and reduce energy consumption by $267,000 /year & reduce water consumption by 1,300,000 gal/yr. The annual energy cost reductions and life cycle cost analysis are as follows; LAB OUTSIDE AIR MAKE UP The annual energy cost reductions and life cycle cost analysis are as follows; Providing heating and cooling via the geothermal field will reduce water consumption resulting from cooling tower water treatment, blow down, and water evaporation by 748,000 gallons /year. In addition, water treatment chemical usage will be greatly reduced. Water consumption. All of the above options reduce water consumption dramatically. Option #1 combined with the geothermal outside air precooling / preheating option saves the most. Study Summary Option descriptions: The post A Geothermal Feasibility Guide appeared first on Poltrona. |
You are subscribed to email updates from Poltrona » Televisão por Ale Rocha. To stop receiving these emails, you may unsubscribe now. | Email delivery powered by Google |
Google Inc., 1600 Amphitheatre Parkway, Mountain View, CA 94043, United States |
Nenhum comentário:
Postar um comentário